ADAM-5013 3-ch RTD Input Module Features
Channels: 3
Effective resolution: 16-bit
Input connections: 2, 3 or 4 wire
Input type: PT100 or Ni RTD
Isolation voltage: 3000 VDC
Sampling rate: 10 samples/sec. (total)
Accuracy: ±0.1% or better
ADAM-5013 3-ch RTD Input Module Specifications
| General |
| Certifications | CE |
| Connectors | 1 x Plug-in screw terminal (# 14 ~ 22 AWG) |
| Power Consumption | 1.1 W (max.) |
| RTD Input |
| Accuracy | ±0.1% or better |
| Bandwidth | 13.1 Hz @ 50 Hz |
|   | 15.72 Hz @ 60 Hz |
| Channels | 3 |
| CMR @ 50/60 Hz | 150 dB |
| Input Connections | 2, 3 or 4 wire |
| Input Impedance | 2 M. |
| lnput Type | PT100 or Ni RTD |
| NMR @ 50/60 Hz | 100 dB |
| Resolution | 16-bit |
| Sampling Rate | 10 samples/sec. (total) |
| Span Drift | ±0.01° C/° C |
| Zero Drift | ±0.015° C/° C |
| RTD Types and Temperature Ranges |
| IEC RTD 100 ohms | Pt -100° C to +100° C a=0.00385 |
|   | Pt 0° C to +100° C a=0.00385 |
|   | Pt 0° C to +200° C a=0.00385 |
|   | Pt 0° C to +600° C a=0.00385 |
| JIS RTD 100 ohms | Pt -100° C to +100° C a=0.00392 |
|   | Pt 0° C to +100° C a=0.00392 |
|   | Pt 0° C to +200° C a=0.00392 |
|   | Pt 0° C to +600° C a=0.00392 |
| Ni RTD |
|   | Ni -80° C to +100° C |
|   | Ni 0° C to +100° C |
| Protection |
| Isolation Voltage | 3000 VDC |
External links for ADAM-5013
Ordering information for ADAM-5013 3-ch RTD Input Module
| Product code | Product options |
| ADAM-5013 | 3-ch RTD Input Module |